Conventional Fire Detection Center
Conventional DHW / CMSI, the Kara 8 UP control and signaling equipment allows the development of a category A fire safety system (SSI) with type 1 alarm equipment (EA).
It integrates in the same box a conventional control and signaling equipment (ECS) of 8 detection loops conforming to standards NF EN54-2 and 54-4 and a fire safety centralizer (CMSI) composed of a control unit. alarm management (UGA) and 3 safety functions that can be configured for transmission or interruption of current with or without position control.
In accordance with the regulations, these two systems have functional independence (separate power supplies). The Kara 8 UP innovates by its operation under a 12V voltage. Finally, the configuration of the ECS or the CMSI can be done on the keypad on the front panel or by PC via the Kara 8 PC configuration software.
It integrates in the same box a conventional control and signaling equipment (ECS) of 8 detection loops conforming to standards NF EN54-2 and 54-4 and a fire safety centralizer (CMSI) composed of a control unit. alarm management (UGA) and 3 safety functions that can be configured for transmission or interruption of current with or without position control.
In accordance with the regulations, these two systems have functional independence (separate power supplies). The Kara 8 UP innovates by its operation under a 12V voltage. Finally, the configuration of the ECS or the CMSI can be done on the keypad on the front panel or by PC via the Kara 8 PC configuration software.
GENERAL FEATURES | |
Food | |
Operating voltage | 12 V |
Main source | 230 Vac |
Secondary source | 1 maintenance-free lead battery 12 V 7 Ah for DHW 1 12 V 1.2 Ah maintenance-free lead battery for the UGA |
Autonomy | 72h in standby / 1h in safety / 10 minutes in alarm |
Viewer | Large graphic LCD display (16 lines of characters) |
Baltic 512 ECS | 8 buses open or 4 buses looped back |
Baltic 1024 | 16 buses open or 8 buses looped back |
Detection | |
8 detection lines of 32 points | |
Alarm discrimination | |
Double detection | |
Safety | |
1 UGA1 evacuation zone | |
2 independent lines of sound diffusers adjustable timing 0 to 5 minutes | |
3 safety functions configurable on emission or failure with or without position control | |
PHYSICAL CHARACTERISTICS | |
Dimensions | L 506 mm x H 300 mm x D 117 mm |
Net weight | 6.2 Kg (with batteries) |
Protection index | IP 30 |
Material | ABS Color white |
COMPATIBILITY | |
Conventional detectors | 12 V Cap 112, Cap 212 |
DM Nemo C | |
Security and operational alarm reports | FI-REP, Aviso LCD ECS / CMSI and Aviso-E TRE ECS / CMSI |
Whelk and Sirocco sound diffusers | |
Power supplies | Coral 24 or 48V |
Sextant DSVAF / DVAF / DSAF |
Centrale de détection d'Incendie Conventionel
1 file(s) 299.80 KB